Xantrex Technology PV100S-208 manual Electrical Specifications

Models: PV100S-208

1 124
Download 124 pages 2.86 Kb
Page 107
Image 107
Electrical Specifications

System Specifications

Electrical Specifications

Table A-2provides the AC and DC specifications for the PV100S.

Table A-2Electrical Specifications for the PV100S 100 kW Grid-Tied Photovoltaic Inverter

Specification

PV100S-208

PV100S-480

 

 

 

Nominal AC Input Voltage

208 Vac

480 Vac

(+10% to -12% acceptable range)

(183 to 228 Vac)

(422 to 528 Vac)

 

 

 

Maximum AC Output Current

278 Arms

121 Arms

Nominal AC Input Frequency

60 Hz

60 Hz

(+0.5 to -0.7 Hz acceptable range)

(59.3 to 60.5 Hz)

(59.3 to 60.5 Hz)

 

 

 

Output Power

100.0 kW

100.0 kW

 

 

 

Peak Power Tracking Window

330 to 600 Vdc

330 to 600 Vdc

 

 

 

Maximum Open Circuit Voltage

600 Vdc

600 Vdc

 

 

 

Maximum DC Input Current

319 amps

319 amps

 

 

 

Over Voltage, Under Voltage and Frequency Ranges

Table A-3provides the over voltage, under voltage, over-frequency, and under- frequency detection limits for the PV100S. These detection limits have been factory tested and deemed to be in compliance with IEEE-929 and UL 1741 requirements for utility interaction.

Table A-3Over/Under Voltage and Over/Under Frequency Ranges

 

 

PV100S-208

 

PV100S-480

Vac Condition

 

 

 

 

 

 

 

 

 

 

 

 

(% of Nominal)

Voltage Range

Trip Time

Voltage Range

Trip Time

 

 

 

 

 

Vac < 50%

Vac < 104

6 cycles

Vac < 240

6 cycles

50% < Vac < 88%

104

< Vac < 183

2 seconds

240

< Vac < 422

2 seconds

88% < Vac < 110%

183

< Vac < 228

normal operation

422 < Vac < 528

normal operation

110% < Vac < 137%

228

< Vac < 285

2 seconds

528

< Vac < 657

2 seconds

137% < Vac

285

< Vac

2 cycles

657

< Vac

2 cycles

f < rated -0.7

f < 59.3

6 cycles

f < 59.3

6 cycles

f > rated +0.5

f > 60.5

6 cycles

f > 60.5

6 cycles

152379 Rev C

A–3

Page 107
Image 107
Xantrex Technology PV100S-208 manual Electrical Specifications, Over Voltage, Under Voltage and Frequency Ranges