Any State → Fault
If the PV100S encounters a fault, regardless of operating state, it will transition to the Fault state. The PV100S will remain in this state until the fault condition has been remedied and cleared. The Fault Code number will appear on the first line of the LCD. A description of the fault will show on the second line. The third line of the LCD will read “F1 to Clear Fault?”. The fourth line shows the goal state.
Fault: 0070
INTERLOCK ACTIVATED F1 to Clear Fault Goal: PWR Tracking
LCD Display showing Fault Code
UFCU Keypad
Figure 2-8 LCD showing Fault Code
To clear the fault:
1.See Table
2.The ability to clear the fault can only be done from the READ Menu. If a fault occurs while accessing the WRITE Menu, pressing <MENU> once will return to the Read Menu, and “F1 to Clear Fault” will appear on the third line of the LCD display.
Auto-restart Feature
In the event of a utility voltage or frequency excursion outside of those specified in Table
152379 Rev C |