Time Delay for PV

Operation

Table 2-5Write Menu Parameters

 

 

 

 

Default

Maximum

Minimum

Parameter

Description

ID

Units

Value

Value

Value

 

 

 

 

 

 

 

Time Delay for PV

Time delay to transition from PV

39

Seconds

300

1200

0

Wake up

wake up state to PV On-line state.

 

 

 

 

 

 

Once the inverter is in PV Wake

 

 

 

 

 

Displays as:

Up mode, it waits for the amount

 

 

 

 

 

PV T Start:

of time determine by this

 

 

 

 

 

 

parameter before transitioning into

 

 

 

 

 

 

PV on-line mode. During this time

 

 

 

 

 

 

the inverter checks that the PV

 

 

 

 

 

 

voltage is no less than the PV

 

 

 

 

 

 

wake voltage, otherwise it goes

 

 

 

 

 

 

into PV Sleep mode.

 

 

 

 

 

 

 

 

 

 

 

 

Time delay for PV

This is the amount of time the

40

Seconds

300

1200

0

Sleep Test

inverter will be in Sleep Test mode

 

 

 

 

 

Displays as:

if the output power continues to be

 

 

 

 

 

below “PV P Stop”. The inverter

 

 

 

 

 

PV T Stop:

will exit Sleep Test mode towards

 

 

 

 

 

 

on-line mode is the power is over

 

 

 

 

 

 

“PV P Stop” or towards Shutdown

 

 

 

 

 

 

mode is the “PV T Stop” timer

 

 

 

 

 

 

expires.

 

 

 

 

 

 

 

 

 

 

 

 

PV Output Power to

This is the output power trigger

41

KW

1

10.0

0.1

Enter Sleep Test

point for the inverter to transition

 

 

 

 

 

Mode

into sleep test mode. When the

 

 

 

 

 

Displays as:

output power is below the value of

 

 

 

 

 

this parameter the inverter enters

 

 

 

 

 

PV P Stop:

sleep test mode.

 

 

 

 

 

 

 

 

 

 

 

 

Power Tracker

This parameter sets the percentage

42

Percentage

100

110

0

Maximum Output

of maximum rated power the

 

of

 

 

 

Power

inverter will produce when in

 

maximum

 

 

 

 

power tracker mode. For example,

 

output

 

 

 

Displays as:

a 100 Kw system with this

 

power.

 

 

 

I PPT Max:

parameter set to 50 will not

 

 

 

 

 

 

attempt to produce more than 50

 

 

 

 

 

 

Kw.

 

 

 

 

 

 

 

 

 

 

 

 

Manual Current

This parameter sets the percentage

43

Percentage

25

110

0

Output

of maximum out current the

 

of

 

 

 

Displays as:

inverter will attempt to produce

 

maximum

 

 

 

while in manual current mode.

 

output

 

 

 

I Manual:

 

 

current.

 

 

 

 

 

 

 

 

 

 

2–18