Specifications
System Specifications
The PV100S has been designed for photovoltaic power systems, which operate within the following specifications.
CAUTION: Equipment Damage
Operation of the PV100S in a manner other than specified in this manual may cause damage to the PV100S and other system components and will void the terms of the warranty.
Environmental Specifications
The following environmental specifications are the same for both models of the
PV100S 100 kW
Table A-1 Environmental Specifications
Specification | Value |
|
|
Dimensions |
|
Inverter and DC Interface | 82 in H x 60 1/4 in W x 22 in D (208 cm H x 153 cm W x 56 cm D) |
Transformer and AC Interface | 44 in H x 50 in W x 34 in D (112 cm H x 127 cm W x 86 cm D) |
Overall System Footprint: |
|
Layout Option A | 12 ft W x 6 ft L (approximate) (3.6 m W x 1.8 m L) |
Layout Option B | 9 ft W x 7 ft L (approximate) (2.7 m W x 2.1 m L) |
|
|
Weight |
|
Inverter and DC Interface | 1000 lbs (approximate) |
Transformer and AC Interface | 1400 lbs (approximate) |
Overall Weight | 2400 lbs (approximate) |
|
|
Allowable Ambient Temperature |
|
Operating | |
Storage | |
|
|
Relative Humidity | To 95%, |
|
|
Elevation | Power Derated above 6600 ft |
|
|
Clearance (ventilation and | In front of access doors: 36 in (91 cm) |
serviceability) | In front of access panels: 36 in (91 cm) |
| Sides: 12 in (30 cm) |
| Back: 6 in (15 cm) |
|
|
Maximum Distance between Main | 15 ft (4.5 m) |
Inverter Enclosure and AC Interface/ |
|
Transformer Enclosure |
|
|
|
152379 Rev C |