Physical Characteristics

Main Inverter Enclosure

The PV100S Main Inverter Enclosure is NEMA-3R rated and contains the power distribution panel, the converter control unit (CCU2), and power electronics matrix. Also found within the Main Inverter Enclosure are some of the system protection devices (such as the sense and control power fuses).

Power Distribution Panel

This panel contains many of the Electromechanical, protective, and control power components necessary to support the operation of the PV100S.

Converter Control Unit (CCU2)

The CCU2 is a Digital Signal Processor (DSP) based control board that performs numerous control and diagnostic functions associated with PV100S operation. Its most significant tasks are control of PV100S electromechanical components and power electronics converters, signal conditioning for high voltage signal inputs and communication with the Universal Front Panel Control Unit, and system sensors. The CCU2 also contains the necessary DC power supplies to support its operation.

Power Electronics Matrix

The power electronics converter is located at the top of the PV100S main inverter enclosure. The matrix is comprised of six switching transistors (IGBT’s), transistor gate drive electronics, a laminated power bus, DC capacitor bank, and an aluminum extrusion heatsink with a cooling fan. The fan is located above the matrix heatsink.

The PV array is tied logically to the matrix DC bus within the DC interface enclosure. The embedded CCU2 control unit manages the transfer of power between the DC bus and the utility grid.

Inductor Enclosure

The Inductor Enclosure is NEMA-3R rated. It contains the necessary filter components to ensure the PV100S line current meets IEEE-519 (1992, standard Practices and REquirements for Harmonic Control in Electrical Power Systems) and UL 1741 (2001, Static Inverters and Converters for use in Independent Power Systems) harmonic distortion requirements. Mounted on the right side of the lower enclosure is an inductor fan to allow cooling of the line filter components within. This enclosure also serves as the mounting base for the PV100S main enclosure.

152379 Rev C

1–7

Page 29
Image 29
Xantrex Technology PV100S-208 manual Main Inverter Enclosure, Inductor Enclosure, Power Distribution Panel