Description of System Operation
System State: Key Disable
Inverter State: Standby
PV State: Sleep
POWER UP
INITIALIZING
PV contactor opened.
Inverter matrix off.
Grid contactor open.
Green LED on. Red off.
KEY
DISABLE
PV contactor open. Inverter matrix off. Grid contactor open.
Enable Key
|
|
| Inverter matrix off. Line contactor open | |
System State: Shutdown | SLEEP | PV Voltage > 300V Close K2 | PV Contactor Closed | |
for at least 10 |
|
| ||
Inverter State: Standby |
|
| ||
seconds |
|
| ||
PV State: Sleep | PV Voltage < 50V (300V - 250V margin) | PV Contactor Open | ||
|
| |||
PV Voltage > 440V |
|
| ||
(PV V START) |
|
| ||
System State: Shutdown | WAKE UP | PV Voltage < 440V (PV V Start) |
| |
Inverter State: Standby | for 5.0 min. |
| ||
|
| |||
PV State: Wake Up | (PV T START) |
| State | |
Grid Contactor K1 Close |
| |||
| Sleep | |||
System State: Shutdown | K1 Settle |
| ||
|
|
| ||
Inverter State: Main Settling | for .5 seconds |
| to | |
PV State: Wake Up |
| |||
Inverter Matrix On | PV Voltage < 300V (Min. Oper.) | Return | ||
| ||||
|
|
| PV Voltage < 300V (Min. Oper.) | |
System State: Power Tracking | ON LINE | PV Power < 1.0kW (PV P STOP) | TEST | |
Inverter State: On Line | for 5.0 min. | |||
| ||||
PV State: On Line |
| (PV T STOP) 5 minutes elapsed | ||
|
| PV Power > 1.0kW (PV P STOP) |
|
System State: Power Tracking
Inverter State: On Line
PV State: Sleep Test
FAULT
PV contactor opened.
Fault from any State Inverter matrix off. Fault Cleared
Grid contactor open.
Red LED on. Green off.
Bold - constant value Italic - User settable.
Underline - Default value.
Figure 2-1 Operating States Flow Chart
152379 Rev C |