Xantrex Technology PV100S-208 1 Operating States Flow Chart, Description of System Operation

Models: PV100S-208

1 124
Download 124 pages 2.86 Kb
Page 43
Image 43
Description of System Operation

Description of System Operation

System State: Key Disable

Inverter State: Standby

PV State: Sleep

POWER UP

INITIALIZING

PV contactor opened.

Inverter matrix off.

Grid contactor open.

Green LED on. Red off.

KEY

DISABLE

PV contactor open. Inverter matrix off. Grid contactor open.

Enable Key

 

 

 

Inverter matrix off. Line contactor open

System State: Shutdown

SLEEP

PV Voltage > 300V Close K2

PV Contactor Closed

for at least 10

 

 

Inverter State: Standby

 

 

seconds

 

 

PV State: Sleep

PV Voltage < 50V (300V - 250V margin)

PV Contactor Open

 

 

PV Voltage > 440V

 

 

(PV V START)

 

 

System State: Shutdown

WAKE UP

PV Voltage < 440V (PV V Start)

 

Inverter State: Standby

for 5.0 min.

 

 

 

PV State: Wake Up

(PV T START)

 

State

Grid Contactor K1 Close

 

 

Sleep

System State: Shutdown

K1 Settle

 

 

 

 

Inverter State: Main Settling

for .5 seconds

 

to

PV State: Wake Up

 

Inverter Matrix On

PV Voltage < 300V (Min. Oper.)

Return

 

 

 

 

PV Voltage < 300V (Min. Oper.)

System State: Power Tracking

ON LINE

PV Power < 1.0kW (PV P STOP)

TEST

Inverter State: On Line

for 5.0 min.

 

PV State: On Line

 

(PV T STOP) 5 minutes elapsed

 

 

PV Power > 1.0kW (PV P STOP)

 

System State: Power Tracking

Inverter State: On Line

PV State: Sleep Test

FAULT

PV contactor opened.

Fault from any State Inverter matrix off. Fault Cleared

Grid contactor open.

Red LED on. Green off.

Bold - constant value Italic - User settable.

Underline - Default value.

Figure 2-1Operating States Flow Chart

152379 Rev C

2–3

Page 43
Image 43
Xantrex Technology PV100S-208 1 Operating States Flow Chart, Description of System Operation, Rev C, Sleep, Return, Test