Xantrex Technology PV100S-208 manual Changing and Displaying WRITE Menu Parameter Values

Models: PV100S-208

1 124
Download 124 pages 2.86 Kb
Page 56
Image 56
Changing and Displaying WRITE Menu Parameter Values

Operation

Changing and Displaying WRITE Menu Parameter Values

Follow the procedure below to change WRITE Menu parameters.

To change WRITE Menu parameters:

1.From the standard display or anywhere in the READ Menu, you may access the WRITE menu parameters by pressing the <MENU> key. This will ask for a password.

2.Enter the password <5><9><4> and press the <ENTER> button.

a)If the wrong password is entered, the display will again prompt the user for the password.

b)If a mistake is made while keying in the password, the /\ or \/ keys may be used as a backspace key.

3.Once within the Write Menu, the first item is the “Set Goal State”. Use the /\ or \/ key on the operator interface keypad to scroll through the WRITE Menu parameters.

a)To change the displayed parameter, press the <ENTER> button.

b)Enter the desired value and press <ENTER>. If the value entered is outside the acceptable range for the parameter, the original value will remain.

c)To leave the WRITE Menu and return to the READ Menu, press the

<MENU> button once and the standard display will reappear on the LCD.

Table 2-5Write Menu Parameters

 

 

 

 

Default

Maximum

Minimum

Parameter

Description

ID

Units

Value

Value

Value

 

 

 

 

 

 

 

Set Goal State

Commands a Goal State.

 

 

 

 

 

Displays as:

 

 

 

 

 

 

Hit ENTER to set

 

 

 

 

 

 

Goal:

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Date

The date is entered

 

 

 

 

 

 

month-day-year (mmddyy):

 

 

 

 

 

Displays as:

April 28, 2005 is entered 042805.

 

 

 

 

 

042805

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Time:

The time is entered in military

 

 

 

 

 

 

hours-minutes-seconds

 

 

 

 

 

Displays as: 163000

(i.e., 24-hour clock): 4:30 pm is

 

 

 

 

 

 

entered 163000.

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Grid

This parameter sets the trigger

32

Percentage

110

110

105

Voltage

point value for “AC voltage High”

 

of

 

 

 

 

(0013) fault. If the grid voltage is

 

Nominal

 

 

 

Displays as:

over this parameter’s value, the

 

voltage

 

 

 

Max AC Volts %:

fault is triggered. The upper limit

 

 

 

 

 

 

of this parameter is restricted by

 

 

 

 

 

 

UL requirements.

 

 

 

 

 

 

 

 

 

 

 

 

2–16

152379 Rev C

Page 56
Image 56
Xantrex Technology PV100S-208 manual Changing and Displaying WRITE Menu Parameter Values, To change WRITE Menu parameters