Table 4-1Fault Codes

Error

 

Fault Type

 

 

 

 

H=Hardware

 

 

 

Code

Fault Source(s)

S=Software

Fault Description

Possible Causes

 

 

 

 

 

 

0075

Shutdown Remotely

S

This fault indicates that the PV100S

Remote Shutdown

 

 

 

has detected that the system was

 

command via the GUI

 

 

 

commanded via the GUI to transition

 

 

 

 

 

to the Shutdown State. This fault is

 

 

 

 

 

not indicative of a failure or

 

 

 

 

 

malfunction, but primarily used to

 

 

 

 

 

disable the system remotely.

 

 

 

 

 

 

 

 

0082

Matrix Not ON

S

This fault indicates that the PV100S

Software acknowledge

 

 

 

has detected that the IGBT matrix

 

bit not accepted

 

 

 

(FPGA) was not enabled after having

FPGA inoperable

 

 

 

sent a command for it to turn on. The

 

 

 

 

 

CCU2 sends an acknowledge bit to

 

 

 

 

 

confirm the command is received.

 

 

 

 

 

This fault is primarily a watch-dog

 

 

 

 

 

between software and hardware to

 

 

 

 

 

ensure control of the IGBT matrix

 

 

 

 

 

(FPGA).

 

 

 

 

 

 

 

 

0083

Matrix Not OFF

S

This fault indicates that the PV100S

Software acknowledge

 

 

 

has detected that the IGBT matrix

 

bit not accepted

 

 

 

(FPGA) was not disabled after having

FPGA inoperable

 

 

 

sent a command for it to turn off. The

 

 

 

 

 

CCU2 sends an acknowledge bit to

 

 

 

 

 

confirm the command is received.

 

 

 

 

 

This fault is primarily a watch-dog

 

 

 

 

 

between software and hardware to

 

 

 

 

 

ensure control of the IGBT matrix

 

 

 

 

 

(FPGA).

 

 

 

 

 

 

 

 

F000

Shipping Software

S

This fault indicates that the PV100S

 

 

 

 

 

has detected that the CCU2 controller

 

 

 

 

 

board has shipping software installed.

 

 

 

 

 

This software is not operational

 

 

 

 

 

software. The correct system

 

 

 

 

 

software for the PV100S must be

 

 

 

 

 

downloaded into the CCU2 controller

 

 

 

 

 

board.

 

 

 

 

 

 

 

 

F100

Software Restarted

S

This fault indicates that the PV100S

 

 

 

 

 

has detected that the system software

 

 

 

 

 

has been re-booted. This is not a true

 

 

 

 

 

fault, and does not effect the

 

 

 

 

 

operation of the PV100S. It is

 

 

 

 

 

primarily used as a watchdog for

 

 

 

 

 

debugging purposes.

 

 

 

 

 

 

 

 