Safety
The terminals are one bolt per pole. See the PV100S 100 kW
5.The AC power conductor wiring interfacing with the AC terminals in the Main Inverter Enclosure are located at
6.The AC power conductor wiring interfacing with the AC terminals in the AC Interface Enclosure are located at
7.The AC neutral conductor from the utility is terminated in the AC Interface Enclosure at the
8.The DC power conductor wiring interfacing with the DC terminals at
(56.5 Nm) for model
9.This product is intended to be installed as part of a permanently grounded electrical system per the National Electric Code ANSI/NFPA 70. A copper ground rod must be installed within three feet of the PV100S enclosure. This is the single point earth ground for the inverter system. The single point ground for the system is to be made at the AC ground bus bar (TB2) in the AC Interface Enclosure. This terminal requires the use of a crimp on type ring terminal or
10.The equipment grounds on the PV100S are marked with this symbol:
11.AC overcurrent protection for the utility interconnect
CAUTION: Fire Hazard
In accordance with the National Electrical Code, ANSI/NFPA 70, connect only to a circuit provided with 400 amperes maximum branch circuit overcurrent protection for model
152379 Rev C | ix |