3M 965DPS instruction manual RFL Multiple Results

Models: 965DPS

1 146
Download 146 pages 50.06 Kb
Page 67
Image 67

RFL Multiple Results

There are two possible formats for displaying the results of an RFL Multiple measurement:

1)The temperature is known. In this case the screen will show the calculated Distance to Strap (the sum of all sections) in the main result box and the “Distance to Fault”on the left on the next line and the “Distance Strap to Fault” on the right on the same line. The screen also shows the number of the faulted section at the lower right side of the screen.

Press the [Tab] key to display the results in ohms. Press the [Enter] key to retest the same pair or the [Return] key to test a new pair.

67

Page 67
Image 67
3M 965DPS instruction manual RFL Multiple Results