OMNISCANNER
Cable under Test
| RX |
850 nm 1300/1310 nm | TX |
2 m Launch Cable
Fixed Connection | Fixed Connection |
2.Do not disconnect the coupler from the black launch cable (it is circled in the graphic).
3.Disconnect the white launch cable from the RX port of the OMNIFiber adapter and the connector adapter (sleeve). Leave the two white connectors dangling.
4.Attach the cable to be tested to the RX port on the OMNIScanner Fiber adapter and the connector adapter (sleeve).
5.Press .
3.7Running a Fiber Autotest
Some Autotests do not have a fixed loss limit. The Optical Link Budget (OLB) is calculated based on the wavelength, the length of the cable, and the number of connectors and splices.
OMNIScanner will automatically display the CONNECTIONS screen if you are running an equation based Autotest (TIA 568A, ISO 11801, or
1.With the Connections: field highlighted, press ENTER. Use the
48