OMNISCANNER

Press (Pairs) to view the NEXT graphs for other pair combinations.

Press (Diagnostics) to display the TDNXT screen, where cabling and/or connection faults can be identified. (See Chapter 6, Diagnostics, for further information.

Press ESC to exit the NEXT screen.

5.3.4ATTENUATION

The Attenuation function measures signal loss in a cable as a function of frequency. OMNIRemote generates and injects a signal at the far end of the cable. OMNIScanner measures the signal at the other end of the cable to determine cable loss.

In the ATTENUATION screen, the worst case margin for all pairs is shown at the top of the screen.

The pairs are displayed in the column on the left side, followed by the Attenuation in decibels (dB), the Attenuation margin/limit values, and the

frequency. The result for each pair is tagged with a PASS or FAIL indicator.

Press (Graph) to display the Attenuation graph for the highlighted pair. The Attenuation is displayed for the frequency indicated by the cursor position.

Press (Pairs) to view Attenuation results for other pairs.