Communicating with Extended-Local I/O

8-9

 

 

Configuring the Controller

as an Extended-Local I/O

Scanner

If you are using block-transfer to a 2760-RB module located in the extended-local rack, make sure you do not set the timeout bit in the block-transfer control file.

To configure the extended-local I/O (channel 2), use the extended-local I/O configuration screen.

This Field

Specifies

Configure by Doing the Following

Diagnostic file

The file containing the channel’s

Cursor to the field enter enter an integer file number (9-999).

 

status information

ATTENTION: Assign a unique diagnostic file to each channel. Do not

 

 

 

 

assign a diagnostic file that is the I/O status file you assigned or any

 

 

other used integer file. Unpredictable machine damage can result.

 

 

Important: You must define a diagnostics file for a channel configured

 

 

for anything but unused (even if you are not using the channel) if you

 

 

want to get status information for that channel.

 

 

 

Scan list

The channel I/O configuration

See the next section for information on creating and modifying a scan

 

 

list.

 

 

 

The scan list for extended-local I/O is similar to the scan list for remote I/O.

The differences are:

The remote I/O scan list displays rack size. The rack size is determined by the chassis size (number of slots) and backplane addressing used by the chassis. The following table explains the relationship among chassis size, backplane addressing and rack size.

Publication 1785-UM012D-EN-P - July 2005

Page 127
Image 127
Bradley Smoker PLC-5 This Field Specifies Configure by Doing the Following, Scan list Channel I/O configuration, List