9-16Communicating with Devices on a DH+ Link

Test Setup

One to 22 PLC-5 controllers were used with one personal computer online. Each PLC-5 controller executes 1K of ladder logic.

Initial testing was done with one PLC-5 controller writing data to another PLC-5 controller. The response time was recorded. Additional PLC-5 controllers were added to the network, each writing the same amount of data to a PLC-5 controller at the next highest station address. Four separate tests were run using data transmissions of 50, 100, 250, and 500 words.

Average DH+ Link Response Time Test Results

This section shows graphically the results of testing performed on a DH+ link where the number of stations and words sent in the message varies.

The figure below shows the average response time of messages of varying sizes on a DH+ link with a varying numbers of stations. It also gives you an idea of the typical response time you can expect on a given DH+ link.

 

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

Response

3.0

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

 

 

 

 

 

X

 

 

 

 

 

 

+

 

 

 

 

 

 

 

(Sec)

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

X

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

+

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

X

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

 

 

 

 

 

 

 

 

 

 

Number of Controllers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of PLC-5 Processors

 

 

 

 

 

 

 

 

 

50 W

100 W

+250 W X 500 W

W=Words

Publication 1785-UM012D-EN-P - July 2005