Processor Status File

B-9

 

 

S:13-S:24

This Word:

Stores

S:13

Program file where fault occurred

 

 

S:14

Rung number where fault occurred

 

 

S:15

VME status file

 

 

S:16

I/O status File

 

S:17Minor fault (word 2)

See also S:10.

 

 

 

 

S:17/00

BT queue full to remote I/O

 

 

S:17/01

Queue full - channel 1A; maximum remote block-transfers used

 

 

S:17/02

Queue full - channel 1B; maximum remote block-transfers used

 

 

S:17/03

Queue full - channel 2A; maximum remote block-transfers used

 

 

S:17/04

Queue full - channel 2B; maximum remote block transfers used

 

 

S:17/05

No modem on serial port

 

 

 

S:17/06

Remote I/O rack in local rack table or

 

Remote I/O rack is greater than the image size. This fault can also be

 

 

caused by the local rack if the local rack is set for octal density scan

 

 

and the I/O image tables are smaller than 64 words (8 racks) each.

 

 

S:17/07

Firmware revision for channel pairs 1A/1B or 2A/2B does not

 

match controller firmware revision

 

 

S:17/08

ASCII instruction error

 

 

S:17/09

Duplicate node address

 

 

S:17/10

DF1 master poll list error

 

 

S:17/11

Protected controller data table element violation

 

 

S:17/12

Protected controller file violation

 

 

S:17/13

Using all 32 ControlNet MSGs

 

 

S:17/14

Using all 32 ControlNet 1771 READ and/or 1771 WRITE CIOs

 

 

S:17/15

Using all 8 ControlNet Flex I/O CIOs

 

 

S:18

Controller clock year

 

 

S:19

Controller clock month

 

 

S:20

Controller clock day

 

 

S:21

Controller clock hour

 

 

S:22

Controller clock minute

 

 

S:23

Controller clock second

 

 

S:24

Indexed addressing offset

 

 

S:25

Reserved

 

 

 

Publication 1785-UM012D-EN-P - July 2005

Page 283
Image 283
Bradley Smoker PLC-5 user manual S13-S24