Communicating with Devices on a Serial Link

10-7

 

 

This Field

Specifies

Configure by Doing the Following

Diagnostic file

The file containing the channel’s

Enter an integer file number (10-999).

 

status information

ATTENTION: Assign a unique diagnostic file to each channel. Do not

 

 

 

 

assign a diagnostic file that is the I/O status file you assigned or any

 

 

other used integer file. Unpredictable machine operation can result.

 

 

Important: You must define a diagnostics file for a channel configured for

 

 

anything but unused (even if you are not using the channel) if you want to

 

 

get status information for that channel.

 

 

 

Enable

Whether the remote mode change

Select ENABLED.

 

option is enabled

 

 

 

 

Mode attention char.

The attention character for the system

 

or the user mode character for remote

 

change

Enter a character. If the attention character you want to use is a control character, specify the ASCII equivalent.

System mode char.

The character to be used with the

 

mode attention character (above)

Enter a character. If the attention character you want to use is a control character, specify the ASCII equivalent.

When the controller encounters the attention character and the system mode character, the controller sets channel 0 communication to system mode. The remote mode change option must be ENABLED.

User mode char.

The character for the mode attention

 

character (above)

Enter a character. If the attention character you want to use is a control character, specify the ASCII equivalent.

When the controller encounters the attention character and the user mode character, the controller sets channel 0 communication to user mode. The remote mode change option must be ENABLED.

Serial Settings

Baud rate

Communication rate for channel 0

Select 110, 300, 600, 1200, 2400, 4800, 9600, or 19.2k bps.

 

Configure all devices in the system for

 

 

the same communication rate

 

 

 

 

Parity

Parity setting for channel 0

Select NONE or EVEN.

 

Parity provides additional message

 

 

packet error detection.

 

 

 

 

Bits per character

Select the number of bits that make up

Select 7 or 8.

 

a transmitted character.

 

 

 

 

Error detect

Whether you want error detection set

 

to BCC or CRC

Select one of the following:

BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to implement in a computer driver.

CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is more complete checking

Configure both stations to use the same type of error checking.

Publication 1785-UM012D-EN-P - July 2005