Communicating with Extended-Local I/O

8-5

 

 

Discrete Data Transfer

The processors scan the extended-local I/O chassis during the housekeeping portion of the program scan. Extended-local I/O discrete data is exchanged between the processor’s data table image and the I/O in the extended-local I/O chassis.

Rack 3

Rack 2

Rack 1

Adapter AdapterAdapter

x y

Data

Exchange

Remote I/O

Buffer

a b x y

Remote I/O

Scan

Extended

-local I/O

Data

Exchange

I/O Image

 

Table

 

Update

 

 

 

 

I/O image

 

 

 

Data

 

 

 

 

 

 

Exchange

 

 

 

 

 

Processor-

Resident

Rack

a

write outputs

b

read inputs

Immediate I/O

1

IOT (x)

IIN (y)

Housekeeping

Logic

Scan

Program Scan

Data exchange occurs during housekeeping. Outputs are written to and inputs read from the I/O image table during the logic scan.

1IIN and IOT data transfer directly to and from I/O modules extended-local I/O chassis.

The time that it takes to scan extended-local I/O chassis is added to the housekeeping time as shown in the following figure.

PLC-5/40L and -5/60L Extended-Local I/O Scan Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logic Scan

Processor

Remote

Processor

+

Extended-

 

 

 

 

 

 

 

 

I/O Buffer

Resident

Local I/O

Housekeeping

 

Checks

 

 

Update

I/O Update

 

Scan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program Scan

Publication 1785-UM012D-EN-P - July 2005