Bradley Smoker PLC-5 user manual Ethernet Channel 2 Configuration Fields

Models: PLC-5

1 388
Download 388 pages 13.97 Kb
Page 178
Image 178

11-4Communicating with Devices on an Ethernet Network

 

Ethernet Channel 2 Configuration Fields

This Field

Specifies

Configure by Doing the Following

 

 

 

Diagnostic file

The file containing the channel’s

Enter an integer file number (10-999). The system creates an integer file

 

status information.

44 words long.

 

 

ATTENTION: Assign a unique diagnostic file to each channel. Do not

 

 

assign a diagnostic file that is the I/O status file you assigned or any

 

 

other used file. Unpredictable machine action can result.

 

 

Important: You must define a diagnostics file for a channel configured

 

 

for anything but unused (even if you are not using the channel) if you want

 

 

status information for that channel.

 

 

 

Ethernet Address

The controller’s Ethernet

Assigned by Rockwell Automation and cannot be changed. Displayed as

 

hardware address.

a set of 6 bytes (in hex), separated by colons.

 

Display only

 

 

 

 

BOOTP Enable

Whether BOOTP is enabled.

Select NO.

 

 

Before you specify No, make sure you have an IP address specified. With

 

 

BOOTP set to No, the controller uses the parameters that you specify

 

 

locally.

 

 

To enable BOOTP, see page 11-5.

 

 

 

IP Address

The controller’s Internet address.

Disable BOOTP first. You cannot manually change the IP address

 

 

with programming software if BOOTP is enabled.

 

 

Enter an address in this form:

 

 

a.b.c.dWhere: a, b, c, d are between 1-254 (decimal)

 

 

You must specify the IP address to have the controller connect to the

 

 

TCP/IP network. Do not use 0 or 255 as a, b, c, or d in the IP address.

 

 

 

Message Connect

The number of milliseconds allowed

Enter a timeout period in milliseconds. (The controller rounds to the

Timeout

for an MSG instruction to establish a

nearest 250 ms.) The valid range for a timeout period is 0-65,535 ms.

 

connection with the destination node.

The default is 15,000 ms.

 

 

 

 

 

Message Reply

The number of milliseconds the

Timeout

Ethernet interface waits for a reply to

 

a command it initiated (through an

 

MSG instruction).

Enter a timeout period in milliseconds. (The controller rounds to the nearest 250 ms.) The valid range for a timeout period is 0-65,535 ms.

The default is 3,000 ms.

Inactivity Timeout

The number of minutes of inactivity

 

before the connection is closed.

Enter a timeout period in minutes. The valid range for a timeout period is 0-65,535 minutes.

The default is 30 minutes.

Publication 1785-UM012D-EN-P - July 2005

Page 178
Image 178
Bradley Smoker PLC-5 user manual Ethernet Channel 2 Configuration Fields, With programming software if Bootp is enabled