10-18Communicating with Devices on a Serial Link

Configure Channel 0 for User Mode (ASCII Protocol)

To configure channel 0 for user mode, use the user mode configuration screen in your programming software.

configure the serial communications as user (ASCII)

specify the details

This Field

Specifies

Configure by Doing the Following

Diagnostic file

The file containing the channel’s

 

status information

Enter an integer file number (10-999).

ATTENTION: Assign a unique diagnostic file to each channel. Do not assign a diagnostic file that is the I/O status file you assigned or any other used integer file. Unpredictable machine action can result.

Important: You must define a diagnostics file for a channel configured for anything but unused (even if you are not using the channel) if you want to get status information for that channel.

Remote mode change

Whether the remote mode change

Select ENABLED or DISABLED.

 

option is enabled

 

 

 

 

Mode attention char.

The attention character for the system

Enter a character. If the attention character you want to use is a control

 

mode or the user mode character

character, specify the ASCII equivalent.

 

 

 

System mode char.

The character for the mode attention

 

character (above)

Enter a character. If the attention character you want to use is a control character, specify the ASCII.

When the controller encounters the attention character and the system mode character, the controller sets channel 0 communication to system mode. The remote mode change option must be ENABLED.

Publication 1785-UM012D-EN-P - July 2005

Page 168
Image 168