F-6Troubleshooting

PROG

R

BATT

PROC

Ethernet Transmit LED

E

MFORCE

RUN

COMM

ENET

TRANSMIT

The PLC-5 Ethernet interface contains an Ethernet Transmit LED that lights (green) briefly when the Ethernet port is transmitting a packet. It does not indicate whether or not the Ethernet port is receiving a packet.

Remote I/O System

ACTIVE

ADAPTER

FAULT

I/O RACK

FAULT

Troubleshooting Guide for the 1771-ASB Series C and D Adapter Module

Indicators

 

Description

Probable Cause

Recommended Action

 

 

 

 

 

 

Active

Adapter

I/O

 

 

 

 

Fault

Rack

 

 

 

 

 

 

 

 

 

On

Off

Off

Normal indication;

 

 

 

 

 

remote adapter is fully

 

 

 

 

 

operational

 

 

Off

On

Off

 

RAM memory fault, watchdog timeout

Replace module.

 

 

 

 

 

 

On

Blink

Off

Module placement error

I/O module in incorrect slot.

Place module in correct slot in chassis.

 

 

 

 

 

 

Blink in unison

Off

Incorrect starting I/O

Error in starting I/O group number or

Check switch settings.

 

 

 

group number

I/O rack address

 

 

 

 

 

 

 

On

On

On

Module not

Incorrect transmission rate setting

 

 

 

 

communicating

 

 

 

 

 

 

 

 

Off

On

On

Module not

Scan switch set for “all but last four

Reset scan switch setting.

 

 

 

communicating

slots” in 1/4 rack

 

 

 

 

 

 

 

Blink

Off

Off

Remote adapter not

Controller is in program or test mode

Fault should be cleared by I/O scanner.

 

 

 

actively controlling I/O

Scanner is holding adapter module in

 

 

 

 

(scanner to adapter

fault mode

 

 

 

 

communication link is

 

 

 

 

 

normal)(1)

 

 

LEDs sequence on/off from

Module not

Another remote I/O adapter with the

Correct the address.

top to bottom

 

communicating

same address is on the link.

 

 

 

 

 

 

 

Publication 1785-UM012D-EN-P - July 2005

Page 354