10-14Communicating with Devices on a Serial Link

This field

Specifies

Configure by Doing the Following

RTS off-delay

The time delay between the time the

 

end of the message transmission and

 

the RTS is de-asserted

 

This time delay is a buffer to make

 

sure that the modem has transmitted

 

the message.

Enter a value 0-255. Limits are defined in 20 ms intervals. For example to wait 40 ms, type 2. The recommended time elapse is 0, unless you are using a modem that automatically returns the CTS as soon as it receives the RTS. If this is the case, enter a delay time to make sure the modem is able to transmit before it attempts to send the message.

ACK timeout

The amount of time you want the

 

controller to wait for an

 

acknowledgment from a remote

 

station to its transmitted message

 

before the controller retries the

 

message or the message errors out

Enter a value 0-65535. Limits are defined in 20 ms intervals. For example to wait 40 ms, type 2. The recommended time elapse is 1 second. Specify 1 second by typing 50.

Reply msg wait

The amount of time the master will

 

wait after receiving an ACK (to a

 

master-initiated message) before

 

polling the slave for a reply

Only define this if you are message-based mode. Enter a valid value 0-65535 (in 20ms increments).

MSG application

The number of seconds within which

Select one of the following:

timeout

the reply message must be received

 

 

before the error bit is set on the

1:30-60 seconds

 

message

2:60-90 seconds

 

The timer starts when the ladder

 

 

 

program first initiates the message

3:90-120 seconds

 

and is restarted if/when the ACK is

 

 

received.

4:120-150 seconds

 

 

5:150-180 seconds

 

 

6:180-210 seconds

 

 

7:210-240 seconds

 

 

 

Polling Settings

 

 

 

 

 

Polling mode

The current value of the polling mode

Select one of the following:

 

 

MESSAGE BASED (ALLOW SLAVE TO INITIATE MESSAGES)—default—

 

 

this option allows remote station initiated messages to be processed

 

 

after all master-initiated messages

 

 

MESSAGE BASED (DO NOT ALLOW SLAVE TO INITIATE MESSAGES)—

 

 

remote station-initiated messages will be acknowledged but not

 

 

processed

 

 

STANDARD (MULTIPLE MESSAGE TRANSFER PER NODE SCAN)—the

 

 

master polls stations based on a list; each station can transmit multiple

 

 

messages per node scan

 

 

STANDARD (SINGLE MESSAGE TRANSFER PER NODE SCAN)—the

 

 

master polls stations based on a list; each station can transmit only one

 

 

message per node scan

 

 

 

Publication 1785-UM012D-EN-P - July 2005