Bradley Smoker PLC-5 Example Calculation, Worst-case controller time is, Variable Value

Models: PLC-5

1 388
Download 388 pages 13.97 Kb
Page 298
Image 298

C-12Maximizing System Performance

Example Calculation

Performance Effects of Online Operations

The worst-case controller time is:

Variable

Value

 

 

periodic input buffer update from remote I/O

10 ms

buffer

 

 

 

one program scan to guarantee inputs received

xx ms

 

 

one program scan to guarantee outputs received

xx ms

 

 

0.18 ms times number of racks

xx ms

 

 

total

 

 

 

For a 3-rack system with a 20 ms program scan, the worst-case controller time is: 10 + 20 + 20 + (0.18 3) = 50.54 ms.

Based on the results of each throughput component calculation presented within the chapter, an example of a worst-case update time calculation is:

Variable

Value

 

 

input card delay

10 ms typical

 

 

I/O backplane

1 ms

 

 

worst-case remote I/O scan time

30 ms

 

 

worst-case controller time

50.54 ms

 

 

worst-case remote I/O scan time

30 ms

 

 

I/O backplane

1 ms

 

 

output card delay

1 ms typical

 

 

total

123.54 ms

 

 

The performance of the PLC-5 controller is affected when you perform online operations via a DH+ link to your program files while in Run mode. Affected activities are:

DH+ messages

serial port messages

channel 3A messages

remote block-transfers

Publication 1785-UM012D-EN-P - July 2005

Page 298
Image 298
Bradley Smoker PLC-5 user manual Example Calculation, Worst-case controller time is, Variable Value