Chapter 3

Placing System Hardware

Using This Chapter

For Information About

Go to Page

Determining the proper environment

3-1

Protecting your controller

3-3

Avoiding electrostatic damage

3-3

Laying out your cable raceway

3-4

Laying out your backpanel spacing

3-5

Grounding your system

3-6

Determining the Proper Environment

Place the controller in an environment with conditions that fall within these guidelines:

Environmental Condition

Acceptable Range

Operating temperature

0 to 60° C (32 to 140° F)

Storage temperature

-40 to 85° C (-40 to 185° F)

Relative humidity

5 to 95% (without condensation)

Separate your programmable controller system from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the controller. This cooling air must not exceed 60° C (140° F) at any point immediately below the controller. If the air temperature exceeds 60° C, install fans that bring in filtered air or recirculate internal air inside the enclosure, or install air-conditioning/heat-exchanger units.

To allow for proper convection cooling in enclosures containing a controller-resident chassis and remote I/O chassis, follow these guidelines.

Publication 1785-UM012D-EN-P - July 2005