Bradley Smoker PLC-5 user manual Extended-Local I/O Troubleshooting, Ethernet Status Indicator

Models: PLC-5

1 388
Download 388 pages 13.97 Kb
Page 353
Image 353

Troubleshooting F-5

Extended-Local I/O Troubleshooting

Indicator Color

Channel Mode

Description

Probable Cause Recommended Action

2

PLC-5/40L and -5/60L processors only

BATT

PROG PROC

R

E

MFORCE

RUN COMM

green

Extended local I/O

active extended-local I/O

normal operation

no action required

(steady)

Scanner

link, all adapter modules are

 

 

 

 

 

 

present and not faulted

 

 

 

 

 

 

 

 

 

 

 

green

 

at least one adapter is

power off at

restore power to the

(blinking

 

faulted or has failed

 

extended-local

 

rack

rapidly or

 

 

 

I/O rack

 

 

slowly)

 

 

communication

restart adapters using

 

 

 

 

fault

 

the controller restart

 

 

 

 

 

 

lockout pushbutton

 

 

 

cable broken

repair cable

 

 

 

 

 

 

 

 

 

 

red

 

hardware fault

hardware error

Turn power off, then on.

(steady)

 

 

 

 

Check that the software

 

 

 

 

 

configurations match the

 

 

 

 

 

hardware set-up.

 

 

 

 

 

Replace the controller.

 

 

 

 

 

 

 

red

Extended local I/O

all adapters faulted

cable

repair cable

(blinking

Scanner

 

 

disconnected or

replace or repair

rapidly or

 

 

 

broken

 

terminator

slowly)

 

 

terminator off

restore power to racks

 

 

 

power off at

 

 

 

 

 

 

extended-local

 

 

 

 

 

 

racks

 

 

 

 

 

 

 

off

 

channel offline

channel is not

Place channel online if

 

 

 

being used

needed

 

 

 

 

 

 

 

Ethernet Status Indicator

Indicator Color

Description

Probable Cause

Recommended Action

STAT

BATT

PROG PROC

R

E

MFORCE

RUN COMM

ENET

STAT

Solid red

Critical hardware fault

Controller requires

Contact your local

 

 

internal repair

Allen-Bradley

 

 

 

representative

 

 

 

 

Blinking red

Hardware or software fault

Fault-code dependent

Contact Allen-Bradley’s

 

(detected and reported via a

 

Global Technical Support

 

code)

 

(GTS)

 

 

 

 

Off

Ethernet interface is functioning

Normal operation

Attach the Controller to an

 

properly but it is not attached to

 

active Ethernet network

 

an active Ethernet network

 

 

 

 

 

 

Green

Ethernet channel 2 is functioning

Normal operation

No action required

 

properly and has detected that it

 

 

 

is connected to an active

 

 

 

Ethernet network

 

 

 

 

 

 

Publication 1785-UM012D-EN-P - July 2005

Page 353
Image 353