B-6Processor Status File

This

 

 

Fault

 

 

Code

Indicates this Fault

And the Fault Is

 

 

 

30

You tried to jump to one too many nested subroutine files

Non-recoverable

 

 

 

31

You did not enter enough subroutine parameters

The fault routine will be executed

 

 

32

You jumped to an invalid (non-ladder) file

but cannot clear major fault bit 2.

 

 

 

 

33

You entered a CAR routine file that is not 68000 code

 

 

 

 

34

You entered a negative preset or accumulated value in a timer instruction

Recoverable

 

 

 

35You entered a negative time variable in a PID instruction

36You entered an out-of-range setpoint in a PID instruction

37You addressed an invalid module in a block-transfer, immediate input, or immediate output instruction

38

You entered a RET instruction from a non-subroutine file

Non-recoverable

 

 

The fault routine will be executed

39

FOR instruction with missing NXT

but cannot clear major fault bit 2.

 

 

 

 

 

40

The control file is too small for the PID, BTR, BTW, or MSG instruction

Recoverable

 

 

 

41

NXT instruction with missing FOR

Non-recoverable

 

 

 

42

You tried to jump to a non-existent label

The fault routine will be executed

 

 

43

File is not an SFC

but cannot clear major fault bit 2.

 

 

 

 

44Error using SFR. This error occurs if:

you tried to reset into a simultaneous path

you specified a step reference number that is not found or is not tied to a step (it is a transition)

the previous SFR to a different step is not complete

45

Invalid channel number entered

Recoverable

46

Length operand of IDI or IDO instruction is greater than the maximum allowed

 

 

 

 

47

SFC action overlap. An action was still active when the step became re-activated

Non-recoverable. The fault

 

 

routine will be executed but

 

 

cannot clear major fault bit 2.

 

 

 