4-24Addressing I/O and Controller Memory

Effectively Using I/O Memory

The PLC-5 controller automatically allocates both an input and output memory location to each I/O location. I/O modules generally only use either the inputs or the outputs. To more effectively use I/O memory, you can use these methods of placing I/O modules.

Use

Application

2-slot

Install 16-point I/O modules as an input module and output module pair in

 

an I/O group. For example, if you place an input module in slot 0, place an

 

output module in slot 1.

1-slot

Install 32-point I/O modules as an input module and an output module

 

pair in an I/O group. For example, if you place an input module in slot 0,

 

place an output module in slot 1.

complementary I/O chassis

You configure complementary chassis with a primary and complement

 

chassis pair. You complement the I/O modules I/O group for I/O group

 

between the two chassis. The I/O modules in the complementary chassis

 

perform the opposite function of the corresponding modules in the

 

primary chassis.

 

By designating a PLC-5 scanner channel as complementary, you can

 

complement racks 1-7. A channel configured for complementary I/O can’t

 

scan racks greater than 7. Those PLC-5 controllers that can address rack

 

numbers greater than 7 can address these racks on another scanner

 

channel which has not been configured as complementary. The remote

 

I/O link device (such as a1771-ASB adapter) must also be configured for

 

complimentary.

 

For more information see the PLC-5 Reference Guide: Configuring

 

Complementary I/O for PLC-5 Controllers, publication 1785-6.8.3.