Bradley Smoker PLC-5 This Word Stores, S2Switch setting information, 2Processor Status File

Models: PLC-5

1 388
Download 388 pages 13.97 Kb
Page 276
Image 276

B-2Processor Status File

This Word

Stores

S:2Switch setting information

 

 

S:2/00

Channel 1A DH+ station number

through

 

S:2/05

 

 

 

S:2/06

Channel 1A DH+ baud rate

 

057.6 kbps

 

1230.4 kbps

 

 

S:2/07

Not defined

S:2/08

 

 

 

S:2/09

Last state

 

0outputs are turned off

 

1outputs retain last state

 

 

S:2/11

I/O chassis addressing

S:2/12

bit 12bit 11

 

 

00illegal

 

101/2-slot

 

011-slot

 

112-slot

 

 

S:2/13

Memory module transfer

S:2/14

bit 14bit 13

 

 

00memory module transfers to controller memory

 

if controller memory is not valid

 

01memory module does not transfer to

 

controller memory

 

11memory module transfers to controller memory

 

at powerup

 

 

S:2/15

Controllercontroller memory protection

 

0enabled

 

1disable

 

 

Publication 1785-UM012D-EN-P - July 2005