C-4Maximizing System Performance

Because the first program scan takes 28 ms, the STI actually occurs 12 ms into the second program scan (28 + 12 = 40, which is the time for the second STI to occur). This example points out that when the STI time period is different than the program scan time, the STI occurs in different places in the program scan. Also note that, due to fluctuations in program-scan times, multiple STIs may be executed during one scan and no STIs during other scans.

Effects of Housekeeping Time

In PLC-5 controllers, basic housekeeping takes 3.5 ms. If it takes the controller 21.8 ms to execute a ladder program, the overall program scan time is 25.3 ms. Any increase in housekeeping affects your program scan.

The following activities can increase housekeeping time:

editing while in remote run mode

putting block-transfer modules in the controller-resident chassis

using the global status flag files

Editing While in Remote Run Mode

The online editing times for ladder programs are as follows:

For this Editing Operation

And this Type of

The Times are

 

 

 

Program

 

 

 

 

 

 

 

Accept Rung (after inserting, modifying,

other than the edited file

0.35 ms per 1000 words

 

or deleting a rung edit)

 

 

 

no labels

3 ms + 0.35 ms per 1000 words

 

 

 

 

 

 

 

 

 

 

 

with labels

3.5 ms + 0.35 ms per 1000 words

 

 

 

 

 

 

Test Edits of the program (impacts one

 

0.2 ms to change the status of

 

program scan)

 

edits from TEST to UNTEST or

 

 

 

 

UNTEST to TEST

 

 

 

 

 

 

Assemble Edits

no edits pending

0.35 ms per 1000 words

 

 

 

 

 

 

 

 

edits pending, no labels

2.0 ms + 1.5 ms per 1000 words

 

 

 

 

 

 

 

 

edits pending, with labels

2.0 ms + 1.9 ms per 1000 words

 

 

 

 

 

 

 

 

 

 

 

IMPORTANT

Editing programs online also delays the execution of PIIs and STIs.

Publication 1785-UM012D-EN-P - July 2005

Page 290