14-2Preparing Power-Up Routines

Allowing or Inhibiting Startup

Defining a Controller Power-Up Procedure

Major fault bit S:11/5 controls whether you can power up the controller in run mode after a loss of power. Do not confuse this bit with user control bit S:26/1.

This Bit

Tells the Controller

user control

whether or not to scan a fault routine upon power up before

S:26/1

returning to normal program scan.

 

 

major fault S:11/5

whether or not to fault at the end of scanning the fault routine.

 

 

After a power loss is experienced while the controller is in run mode, the controller automatically sets major fault bit S:11/5 if user control bit S:26/1 has been set.

If the Fault Routine

Then the Controller

 

Makes S:11/5

 

 

 

 

 

Set (1)

Faults at the end of scanning the fault

 

 

routine

 

 

Leave this bit set to inhibit startup

 

 

 

 

Reset (0)

Resumes scanning the controller memory file

 

 

Reset this bit to allow startup

 

 

 

 

 

 

 

 

You can use JMP and LBL instructions to scan only the

IMPORTANT

portion of the fault routine associated with a particular

 

 

 

fault or power-up condition.

 

 

The user control bits S:26/0 and S:26/1 define how the controller starts in run mode after a power loss or when you switch to run mode from program or test mode.