Processor Status File

B-3

 

 

S:3-10

This Word

Stores

 

S:3 to S:6

Active Node table for channel 1A

 

WordBitsDH+ Station #

 

30-1500-17

 

 

40-1520-37

 

 

50-1540-57

 

 

60-1560-77

 

 

 

S:7

Global status bits: (See also S:27, S:32, S:33, S:34, and S:35)

 

S:7/0-7

rack fault bits for racks 0-7

 

S:7/8-15

unused

 

 

S:8

Last program scan (in ms)

 

 

S:9

Maximum program scan (in ms)

 

 

S:10Minor fault (word 1)

 

See also S:17

 

 

 

 

 

S:10/00

Battery is low (replace in 1-2 days)

 

 

S:10/01

DH+ active node table has changed

 

 

S:10/02

STI delay too short, interrupt program overlap

 

 

S:10/03

memory module transferred at power-up

 

 

S:10/04

Edits prevent SFC continuing; data table size changed during

 

program mode; reset automatically in run mode

 

 

S:10/05

Invalid I/O status file

 

 

 

S:10/06

reserved

 

 

 

S:10/07

No more command blocks exist to execute block-transfers

 

 

S:10/08

Not enough memory on the memory module to upload the program

 

from the controller

 

 

S:10/09

No MCP is configured to run

 

 

S:10/10

MCP not allowed

 

 

S:10/11

PII word number not in local rack

 

 

 

S:10/12

PII overlap

 

 

 

S:10/13

no command blocks exist to get PII

 

 

S:10/14

Arithmetic overflow

 

 

S:10/15

SFC “lingering” action overlap - step was still active when step

 

was reactivated

 

 

 

 