Troubleshooting

F-9

 

 

 

 

 

 

 

 

 

 

 

Extended-Local I/O System

Troubleshooting Guide for the 1771-ALX Adapter Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTIVE

 

 

 

 

 

 

 

 

 

 

 

ADAPTER

 

 

 

 

 

 

 

 

 

 

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

I/O RACK

 

 

 

 

 

 

 

 

 

 

 

 

FAULT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicators

 

 

Description

 

Probable Cause

Recommended Action

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Active

Adapter

 

I/O

 

 

 

 

 

 

 

 

 

 

Fault

 

Rack

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

Off

 

Off

Normal indication;

 

 

 

 

 

 

 

 

 

 

 

remote adapter is fully

 

 

 

 

 

 

 

 

 

 

 

operational

 

 

 

 

 

 

 

Off

On

 

Off

Local adapter fault (1)

Local adapter not operating; it will

Cycle power to the chassis to clear the

 

 

 

 

 

 

 

 

 

 

stay in fault mode until fault is

adapter fault.(2) Replace adapter if fault

 

 

 

 

 

 

 

 

 

 

corrected

does not clear.

 

 

 

 

 

 

 

 

 

 

 

Off

Off

 

On

I/O chassis fault 1

Problem exists between:

Cycle power to the chassis to clear a

 

 

 

 

 

 

 

 

 

 

adapter and module in chassis; the

problem resulting from high noise.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module will stay in fault mode until

remove and replace all I/O modules one at a

 

 

 

 

 

 

 

 

 

fault is corrected

 

 

 

 

 

 

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

shorted printed circuit board runs on

 

 

 

 

 

 

 

 

 

 

 

replace adapter

 

 

 

 

 

 

 

 

 

 

 

backplane or I/O module

 

 

 

 

 

 

 

 

 

 

 

• If problem does not clear, something is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wrong in chassis or I/O module

 

 

 

 

 

 

 

 

 

 

 

Blinking

Off

 

Off

Outputs are reset

Controller is in program or test mode

None

 

 

 

 

 

 

 

 

 

 

Local I/O Scanner is holding adapter

 

 

 

 

 

 

 

 

 

 

 

 

module in fault mode

Fault should be cleared by extended-local

 

 

 

 

 

 

 

 

 

 

I/O scanner.

 

 

 

 

 

 

 

 

 

Blinking alternately

 

Off

Adapter module not

Controller restart lockout switch on

Press chassis reset button to clear lockout

 

 

 

 

 

actively controlling I/O 1

chassis backplane switch assembly

feature or cycle power; if after repeated

 

 

 

 

 

 

 

Adapter module in

on(3)

attempts indicators are still blinking, check

 

 

 

 

 

controller restart lockout

 

 

that adapter module was reset by

 

 

 

 

 

 

 

mode (adapter to

 

 

controller/scanner, then immediately

 

 

 

 

 

 

 

scanner link is normal)

 

 

faulted.

 

 

 

 

 

 

 

 

 

 

Off

Off

 

Off

No power or no

 

Power supply fault

Check power supply, I/O cable and power

 

 

 

 

 

communication.

 

 

 

supply cable connections, and make sure

 

 

 

 

 

 

 

 

 

 

adapter module is fully seated in chassis.

 

 

 

 

 

 

 

 

 

On

Blinking

 

Off

Module placement error

Incorrect placement of high-density

Verify addressing modes and switch

 

 

 

 

 

 

 

in extended-local I/O

modules

settings.

 

 

 

 

 

 

 

chassis

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis.

(2)If a fault occurs and the controller is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by switch 1 (the last state switch) on the chassis backplane.

(3)The I/O chassis is in faulted mode as selected by switch 1 (the last stare switch) on the chassis backplane.

Publication 1785-UM012D-EN-P - July 2005