Bradley Smoker PLC-5 user manual Interpreting Ethernet Status Data, F00A, Active screen

Models: PLC-5

1 388
Download 388 pages 13.97 Kb
Page 208
Image 208

11-34Communicating with Devices on an Ethernet Network

Code - Hexadecimal

Description

(word 1 of the control block)

(displayed on the data monitor screen)

 

 

9000

Remote node cannot buffer command

 

 

B000

Controller is downloading so it is inaccessible

 

 

F001

Controller incorrectly converted the address

 

 

F002

Incomplete address

 

 

F003

Incorrect address

 

 

F006

Addressed file does not exist in target controller

 

 

F007

Destination file is too small for number of words requested

 

 

F00A

Target controller cannot put requested information in packets

 

 

F00B

Privilege error, access denied

 

 

F00C

Requested function is not available

 

 

F00D

Request is redundant

 

 

F011

Data type requested does not match data available

 

 

F012

Incorrect command parameters

 

 

F01A

File owner active – the file is being used

 

 

F01B

Program owner active – someone is downloading, online

 

editing, or set the program owner with APS in the WHO

 

Active screen

Interpreting Ethernet Status Data

Monitor the status of Ethernet PLC-5 controllers by accessing the Ethernet channel 2 status screen of your programming software. The diagnostic counter data displayed is stored in the diagnostic file defined on the Ethernet channel 2 configuration screen.

Publication 1785-UM012D-EN-P - July 2005

Page 208
Image 208
Bradley Smoker PLC-5 user manual Interpreting Ethernet Status Data, F00A, Active screen