8-12Communicating with Extended-Local I/O

Use the following table for information about creating/modifying your scan list:

To:

Do the Following

Create a scan list

Make sure the controller is in Remote Program or Program mode.

 

1.Make sure that you defined an I/O status file on the controller configuration

 

screen.

 

2.Accept any edits made to the channel configuration.

 

3.Use the autoconfiguration function

 

If you have errors when you accept edits, clear the scan list and accept edits again.

 

If some or all adapters are not on the scan list and should be, check to see that they

 

are powered-up and that the channels are connected properly. Also verify that all

 

switch settings on the adapters are set correctly.

 

 

Insert an entry into the

Make sure the controller is in Remote Program, Program, or Remote Run mode.

scan list

1.Position the cursor at the place on the scan list where you want to insert an entry.

 

 

2.Insert an entry into the list and enter the appropriate values for the list.

 

Important: If incorrect information is entered for an entry, the controller will not

 

display the new configuration when you save edits.

 

 

Delete an entry for the

Make sure the controller is in Remote Program, Program, or Remote Run mode.

scan list

1.Position the cursor at the place on the scan list where you want to delete an entry.

 

 

2.Delete the entry from the list.

 

Important: If incorrect information is entered for an entry, the controller will not

 

display the new configuration when you save edits.

 

 

Monitoring Extended-Local I/O Status

To monitor extended-local I/O of PLC-5/40L and PLC-5/60L controllers, use the extended local I/O status screen in your programming software.