Preparing Fault Routines

15-3

 

 

To decide how to set this switch, evaluate how the machines in your process will be affected by a fault. For example:

how will the machine react to outputs remaining in their last state or to outputs being automatically de-energized?

what is each output connected to?

will machine motion continue?

could this cause the control of your process to become unstable?

To set this switch, see Appendix E.

Fault in a Controller-Resident or Extended-Local I/O Rack

If a problem occurs with the chassis backplane, the controller sets the appropriate minor fault bit (S:7/0-7) and continues scanning the program and I/O. As soon as this bit is set, the outputs for that rack are reset. However, the controller continues normal run-time operation.

The outputs are enabled again only if the faulted rack condition is cleared. For example, if a local I/O module faults, all outputs in that rack are reset and the controller continues executing the program scan. Outputs will be enabled only after the faulted module is removed.

Your ladder program should monitor the I/O rack fault bits (S:7/0-7) and take the appropriate recovery action.

ATTENTION

If a controller-resident local I/O rack fault occurs and you have no recovery methods, the input image table and outputs for the faulted rack remain in their last state. Potential injury to personnel and damage to the machine may result.

Fault in a Remote I/O Chassis

A remote I/O rack fault can be a loss of communications with the remote I/O device or a problem with the remote I/O device itself. When the controller detects a remote I/O rack fault, the controller sets an I/O rack fault bit in the controller status table. The controller then continues scanning the program and controlling I/O.

Publication 1785-UM012D-EN-P - July 2005

Page 241
Image 241
Bradley Smoker PLC-5 user manual Fault in a Remote I/O Chassis, Preparing Fault Routines