10-10Communicating with Devices on a Serial Link

This Field

Specifies:

Configure by Doing the Following

User mode char.

The character for the mode attention

 

character (above)

Enter a character. If the attention character you want to use is a control character, specify the ASCII equivalent.

When the controller encounters the attention character and the user mode character, the controller sets channel 0 communication to user mode. The remote mode change option must be ENABLED.

Serial Settings

Baud rate

Communication rate for channel 0

Select 110, 300, 600, 1200, 2400, 4800, 9600, or 19.2k bps.

 

Configure all devices in the system for

 

 

the same communication rate

 

 

 

 

Parity

Parity setting for channel 0

Select NONE or EVEN.

 

Parity provides additional message

 

 

packet error detection.

 

 

 

 

Bits per character

Select the number of bits that make up

Select 7 or 8.

 

a transmitted character.

 

 

 

 

Error detect

Whether you want error detection set

Select one of the following:

 

to BCC or CRC

BCC: the controller sends and accepts messages that end with a BCC byte

 

 

 

 

for error checking. BCC is quicker and easier to implement in a computer

 

 

driver.

 

 

CRC: the controller sends and accepts messages with a 2-byte CRC for

 

 

error checking. CRC is more complete checking

 

 

Configure both stations to use the same type of error checking.

 

 

 

Stop bits

Match the number of stop bits to the

Select 1, 1.5, or 2.

 

device with which you are

 

 

communicating

 

 

 

 

Control line

Select the mode in which the driver

 

operates.

Select a method appropriate for your system’s configuration:

If you are not using a modem, choose NO HANDSHAKING.

If you are using a full-duplex modem, choose FULL-DUPLEX.

Option Settings

Station address

The station address for channel 0 on

Enter a valid DF1 address (0-376 octal).

 

the DF1 half-duplex link

 

 

 

 

DF1 retries

The number of times the remote

Enter a value 0-255. The recommended setting is 3.

 

station retries a message before the

 

 

station declares the message

 

 

undeliverable

 

 

 

 

Publication 1785-UM012D-EN-P - July 2005