Image 80

6-8Communicating with Remote I/O

ATTENTION

Assign a unique diagnostic file to each channel. Do not assign a diagnostic file that is the I/O status file you assigned or any other used integer file. Unpredictable machine damage can result.

In this Field

Define

By Doing the Following

Diagnostic file

The file containing the channel’s status

Cursor to the field, type an integer file number (9-999)

 

information:

 

 

messages received

 

 

messages sent

 

 

messages received with error

 

 

unable to receive

 

 

sent with error

 

 

rack retries

 

Baud rate

The communication rate for the remote

Cursor to the field and select the desired rate.Available rates are:

 

I/O scanner mode link

57.6, 115.2, and 230.4 kbps.

IMPORTANT

You must define a diagnostics file for a channel configured for anything but unused (even if you are not using the channel) if you want to get status information for that channel.

Publication 1785-UM012D-EN-P - July 2005

Page 80
Image 80