Compaq HSZ80 manual Optimum Operating Environmental Specifications

Models: HSZ80

1 386
Download 386 pages 41 Kb
Page 339
Image 339

B–3

Environmental Specifications

The HSZ80 array controller is intended for installation in a Class A computer room environment.

The optimum environmental specifications are listed in Table B–2;the maximum operating environmental specifications are listed in Table B–3;and the maximum nonoperating environmental specifications are listed in Table B–4.These are the same as for other Compaq storage devices.

Table B–2

Optimum Operating Environmental Specifications

 

 

Condition

Specification

 

 

Temperature

+18° to +24°C (+65° to +75°F)

Temperature rate of change

11°C (20°F per hour)

Relative humidity

40% to 60% (noncondensing) with a step change of 10% or less

 

(noncondensing)

Altitude

From sea level to 2400 m (8000 ft)

Air quality

Maximum particle count 0.5 micron or larger, not to exceed 500,000

 

particles per cubic foot of air

Inlet air volume

0.026 cubic m per second (50 cubic ft per minute)

 

 