5–105

SET EMU

Sets operating parameters for the environmental monitoring unit (EMU).

Syntax

SET EMU

Switches

The SENSOR and FANSPEED switches control both the master and slave EMU settings. The EMU within the primary cabinet (master) instructs the EMUs within the other cabinets to operate at the same SENSOR and FANSPEED settings to which the master EMU is set.

SENSOR_1_SETPOINT=nn

SENSOR_2_SETPOINT=nn

SENSOR_3_SETPOINT=nn

SENSOR_x_SETPOINT=35 (Default)

Sets the acceptable temperatures (in Celsius) at which the subsystem operates. Sensor 1 and Sensor 2 set the maximum operating temperature for the primary subsystem cabinet. Sensor 3 sets the maximum operating temperature for the EMU unit. The allowable range for the setpoint is 0°C (32°F) to 49°C (120°F). The EMU determines the default setpoint for all three sensors.

Table 5–7lists the valid EMU set-point temperatures in both Fahrenheit and Celsius.

Compaq HSZ80 Array Controller ACS Version 8.3 Configuration and CLI Reference Guide

Page 291
Image 291