3. Insert the first output field and the respective key functions into the picture:
●Insert an output field type, Output Word (unsigned), with the following parameters:
Position: | 24,3 |
Number of Digits: | 5 |
Places after the dec. point: | 0 |
Character Size: | 1 |
Field Width: | 5 |
Tagname: | SETWORD |
Display leading zeros? (Y/N): | N |
Scaling ? (Y/N) | No |
●In order to write to memory location SETWORD by pressing F1, a function must be assigned to a function key. Assign the key that will be defined as function key F1 (see “Defining Key Assignments”), using the key function Set Word with the following parameters:
Tagname: | SETWORD |
Value 1: | 10000 |
It is not necessary to define the parameters Tagname for Completion and Value for
Completion.
Press F5 Key to display the LED/Key function menu. Step 6 under “Clock Picture” (see page
4. Insert the second output field and its key function into the picture:
●Insert an output field of type Output Word (unsigned) with the following parameters:
Position: | 24,4 |
Number of Digits: | 5 |
Places after the dec. point: | 0 |
Character Size: | 1 |
Field Width: | 5 |
Tagname: | TOGGWORD |
Display leading zeros? (Y/N): | No |
Scaling ? (Y/N) | No |
●To switch the memory location TOGGWORD between two different values by pressing F2, a key function must be assigned to this function key. Assign the key function Toggle Word to the key that will be defined as function key F2 (see “Defining Key Assignments”), with the following parameters.
Tagname: | TOGGWORD |
Value 1: | 0 |
Value 2: | 20000 |
There is no need to define parameters Tagname for Completion and Value for Completion. Step 6 of section “Clock Picture” describes how to assign a key function to a single key (see page
6 - 46 | PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 |