Editing the Alarm System

The alarm system can be accessed via the Alarm System option in the Edit menu, or by pressing the key combination Ctrl + A. The alarm system basic configuration screen appears:

For the demo project, no printer will be supported. To disable the printer, follow these steps:

1. Press F1 Edit to begin editing the Alarm System Basic Configuration.

2. Move the cursor to the Printer Available field, type NO, and press ↵.

3. Press F4 Accept to complete the editing step.

4. Now press F4 Alarm Group List to call up a directory of alarm groups. By default, this directory contains two predefined groups:

5. In order to display alarms from the PLC, which are stored in the Panel, an alarm group must be inserted. To do this, follow these steps:

A. Press F2 Ins. The Alarm Group Definition window appears:

6 - 58

PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995

GFK-1115

Page 154
Image 154
GE Monogram GFK-1115 manual Editing the Alarm System, Press F2 Ins. The Alarm Group Definition window appears