E. Now you can display a list of all alarms in this group by pressing the F5 Alarm List key
while in the Alarm Group List window. (Press PgeDn to view the remainder of the Alarm List window.)
F. You can change the sequence of the alarms and the definition of each individual alarm in this list by pressing F1 Edit.
G. Press F10 Exit repeatedly until the main menu appears again.
Activating the Alarm System
The alarm system still has to be activated in the project definition. To change the project definition, follow these steps:
1. Access the project definition using option Project in the Edit menu, or by using key combination Ctrl + P:
2. Press function key F1 Project Def.
3. Move the cursor to the line Enable Alarm System.
4. Enter Y and confirm it by pressing ↵.
5. End the project definition with F4 Accept.
6. Close the project editor with F10 Exit. The main menu appears again.