5.Grasp the top section near the thumbscrews and lift it off the bottom section. Separate the cooling unit section to access the blower.
6.
Loosen the thumbscrews
Figure 14: Thumbscrews on blower
7.Removing the top from the cooling unit
6.Lift the blower off the mounting pins and detach the electrical connector.
7.Attach the electrical connector of the new blower and set the blower in place. Be sure you position the blower onto the mounting pins.
Figure 15: Positioning the blower onto mounting pins
Be sure the blower points outward, towards the handle.
8.Place the top section of the cooling unit onto the bottom section and tighten the thumbscrews.
9.Carefully slide the cooling unit into the enclosure.
10.Gently press the handle in and upward until it locks.
Figure 16: Locking the cooling unit handle
11. Verify that the Fan LEDs are green.
This completes the blower replacement procedure.
76 | EXCEL MERIDIAN DATA |