8.6.2 G-50A data collection (Step 1)

It is possible to collect the system information (group information, interlocking ventilation unit setting information, etc.) set for the G-50A with the integrated centralzed control software TG-2000A during the initial setting.

Caution:

Note that using the G-50A data collecting function may cause the system information possessed in the TG -2000A to be completely cleared. When the information is collected, execute the initial setting again as it is written over the G-50A information.

It can only collect the information when all the G-50A units are connected.

It is recommended to execute this function after the test operation of the air conditioner and the G-50A have been completed normally.

Collect the information from the G-50A during the initial setting.

[Procedure]

1)Select the [Collecting of information from G-50] button.

To collect the system information from the G-50A during the initial setting, click the [Collecting of information from G-50] button.

After completing the information collecting, the opera- tion advances automatically to the next step. Wait a moment, as it takes time for information collecting.

*When the [Cancel] button is clicked, this setting is terminated to return to the initial screen.

G-50A Data collection screen

Skip the collecting information from the G-50A. [Procedure]

1)Select the [Next] button.

If it is not necessary to collect the informat ion, click the [Next] button.

8.6.3 Unit composition set-up (Step 2)

It is possible to confirm and change the configuration of the unit in each G-50A .

G-50A Selection:

Selected unit icon:

Displays the icons (symbols)

Select the G-50 No.

such as the indoor unit, outdoor

 

unit, remote controller, system

 

remote controller, etc. and their

 

names.

Unit configura-

 

tion table:

 

Displays the system

 

configuration unit of

 

the G-50 concerned.

 

Unit configuration address setting

 

Confirm the unit configuration.

 

[Procedure]

 

1)Select the G-50 No. with the “￿ /￿“ buttons.

In this case, use the “ ￿/￿“ buttons to select the G-50A No. desired to confirm the unit configuration.

2)Select the [OK] button after checking the unit configuration of each G-50A .

If it is not necessary to change the unit configuration of each G-50A when it is checked, click the [OK] button. *When the [Cancel] button is clicked, this setting is terminated to return to the initial window.

29

Page 32
Image 32
Mitsubishi Electronics TG-2000A operation manual 2 G-50A data collection Step, Unit composition set-up Step