8 . 8 . 3 S e t-up for the Name and the Maximum Integrated Value of WHM (Step 2)

Set the WHM name, location, and maximum integrated value

1)Enter the WHM name and location.

Enter the connected WHM name and location.

2)Set the maximum integrated value.

Use the “/” button or numeric input to set the WHM maximum integrated value.

3)Click [Finish] button.

At the end of setting, click the [Finish] button.

*If the [Cancel] button is clicked, the settings are interrupted and the screen returns to the initial window.

Name and maximum integrated value settings

Note:

A name and location up to 16 characters long can be entered.

Always set the WHM maximum integrated value. If the correct maximum integrated value is not set, the energy monitoring functions will not operate normally.

When the WHM maximum integrated value is 0, a warning is displayed. Set the WHM maximum integrated value.

[Reference]

Shows the communication parameters that must be set at the watt hour meter used.

Model

Baud rate

Parity

Stop bit

Notes

 

 

 

 

 

 

 

 

 

 

Power Rail 323

9600 bps

Fixed

Fixed

 

AEM31D/485

Fixed

Fixed

Fi xed

 

 

 

 

 

 

 

CVM-BC-ITF-RS485-C2

9600

bps

None

1 b i t

 

 

 

 

 

 

 

ED 39din -485

9600

bps

None

1 b i t

BCD used as communications protocol.

 

 

 

 

 

 

Items other than the above do not have to be set because they are fixed for each watt hour meter.