2.3Restrictions

The following restrictions apply to the TG -2000A application.

(1) System configuration limits

Number of units

Notes

 

G-50A

 

Max. 40 units

 

G-50A Ver.

2. 10 or higher

 

 

Indoor unit

 

Max. 50 units/G-50A

 

Max. 2000 units (including all IC, KIC, AIC, LC, and FU)

 

 

[Symbol]IC: Indoor unit, LC: LOSSNAY, FU: OA processing unit, AIC: “A” controller,

 

 

KIC: “K” controller

 

 

 

 

 

 

(2) Group setting restrictions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Restrictions

 

 

Note

 

 

 

 

 

 

 

 

 

Remote controls

2 per group

 

 

* Other remote controls besides M -NET

 

 

 

 

 

 

 

 

 

 

type will not work

 

 

Number of indoor units

1 to 16

 

 

*

IC, AIC, KIC, or LC cannot be used

 

 

connected to a group

 

 

 

 

 

within the same group. It is not pos -

 

 

 

 

 

 

 

 

 

 

sible for group settings to span G-50A

 

 

Number of SC and RC

4 per group

 

 

*

The number of G-50A is not included

 

 

connected to a group

 

 

 

 

 

 

 

 

 

Groups per floor

Max. 50 groups per floor

 

Up to 50A groups can be displayed on

 

 

 

 

 

 

 

 

 

one floor of the whole building window.

 

*1 The ME remote controller and MA remote controller cannot be used together for the same group. *2 Set the same function unit for the group.

[Symbol]SC: System controller, RC: Remote controller

(3)Block setting

The block comes in two types, operation block and charge block.

The operation block is an aggregate of groups, and it is possible to set a different model group for the same operation block.

The charge block consists of an aggregate of operation blocks.

Group

Block for operation

Block for charging

(4)Notes on using K control models

When using a K transmission converter (model name: PAC-SC25KA, PAC-SC25KAA(-E)) to manage K control models, take note of the following. See the documentation provided with the Ktransmission converter for more detail.

The address of the K transmission converter will be the smallest address of the K control model + 200.

Set the K control model addresses so that they are larger than the M transmission model addresses.

When setting a group containing K control models, make the group number the same as the smallest unit address in the group.

(5)Notes on using A control mode

Use the A/M NET Adapter (model name: PAC-SF48MA(-E)). Set the group to “Group with only A control”.

(6)Countermeasure when an error occurs

Note that each control or function may not operate properly when rebooting (*1) or when a fault occurs in the centralized Controller G-50A. Since each error is displayed when it occurs, it is recommended to solve the faults quickly.

*1 Indicates that the system is restarting.