Change the unit configuration. [Procedure]

1)Select the G-50 No. with the “/ “ buttons.

In this case, use the “/ “ buttons to select the G-50A No. desired to change the unit configuration.

2)Delete/add the unit icon.

Unit icon deletion:Click the unit icon to be deleted.

Unit icon addition:Click the unit icon to be added from the selected unit icon column to set it to the selected state.

(The symbol of the selected unit is displayed by the pointer.) When the address column to be added is clicked, the unit icon is displayed.

Table: Icon symbol and unit name

Icon

Name

Address range

 

 

 

 

 

 

IC

Indoor unit

1 to 50

LC

LOSSNAY

 

 

 

 

FU

OA processing unit

 

KIC

“K” Control Units

 

AIC

“A” Control Units

 

 

 

 

OC

Outdoor unit

51 to 100

BC

BC controller (master)

 

BS

BC controller (slave)

 

 

 

 

OS

Subsidiary outdoor unit

 

RC

ME remote controller (compact remote controller) /

101 to 200

 

LOSSNAY remote controller

 

SC

System controller (Including GR, SR, and AN)

201 to 250

 

 

 

GR

Group remote controller

 

SR

System remote controller

 

AN

On/Off controller

 

 

 

 

KA

K -transmission converter

(201 to 250)

TR

Central controller (MJ-103)

(201 to 250)

G-50

Central controller G-50

(0, 201 to 250)

 

 

 

??

Unconfirmed unit

(1 to 250)

3)Select the [OK] button.

After fully completing the unit icon change, click the [OK] button.

Note:

When the system information is collected from the G-50A, all the SR, GR, and AN display "SC". It is possible to change the icon to that of the system controller actually connected. When the icon is changed, it is possible to display the unit in which the error occurred with the type easily discriminated.

Delete the "??" icon displayed, and set the original icon. Note that it is unable to advance to the next step if the "??" icon exists.