11.3 Charging Test Run Check

Note:

The charging test run check takes at least 3 days.

(Check the contents for the first day before 4:00. If the air conditioner has been stopped during the period from 0:00 to 4:00, it is possible to conduct the checking in two days.)

Leave enough time for the transfer when carrying out the charging test operation.

Carry out this check when system is modified while the system is up and running.

Flow of charging test run

 

Test item

Comment

 

 

 

Day 1

(1) Check the charge setting details on the

* After checking the setting, allow

 

man-machine

TG-2000A to operate as it was .

 

 

 

Day 2

(2) Check the meter values of the watt hour meter

* Items (2) and (4) are performed

 

(No. 1)

for charge calculation with WHM

 

(3) Let the air conditioners run

connected.

 

(4) Check the meter values of the watt hour meter

 

 

(No. 2)

 

Day 3

(5) Check the results of charging division

* When the check result is OK,

 

(6) Check the settlement results

item (8) is performed.

 

(7) Decision check

 

 

(8) Change to actual operation setting

 

Man-machine: Personal computer for integrated centralized control software TG -2000A

11.3.1 Charging (No WHM connection) Test Run Check

Charging test run check sheet (Charging (No WHM connection)) Perform the charging test run check after the test run check is complete.

Follow the order of testing prescribed by the charging test run check sheet and check the following items: (1) t o (6).

Note:

When the results do not conform to the decision standards outlined in (5), fix the problem and restart the check from (1).

(1)Check the charge setting details on the man-machine.

Write the charge setting details down on the charging test run check sheet. Check the details of the data to ensure charging is operating correctly.

Division mode selection (S ee section 8. 9.2)

àSet the mode used

Charge setting (See section 8.9. 9)

àSet the time using the with within/outside setting to perform the charging test run check. (Same unit cost for the With daytime/nighttime setting, Without weekend charge setting, and Without seasonal charge setting)

For the unit cost, set both within and outside to 10.

Execute the setting so that the test run time for the air conditioner is carried over both within and outside.

 

 

Test run period of air

 

 

 

 

Example) 11:00 conditioner

13:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside

 

Within

 

Outside

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12:0014:00

Settlement day setting (See 9 . 3 in Management).

àFor charging test run check purposes, set it to the next day

Charge block setting (See section 8.9.7)

àSet the charge block to be manipulated

*To set the charging block, (operation block) must be set. (See section 8. 7 . 7) Check the following details for each indoor unit.

Addresses of the outdoor units in the same refrigerant system (See section 8. 6 . 4)

Performance of indoor units (See section 8. 9 . 6)

82

Page 85
Image 85
Mitsubishi Electronics TG-2000A Charging Test Run Check, Charging No WHM connection Test Run Check, Test item Comment