8.6.5 Set-up of group (Step 4)

It is possible to confirm and change the group information of the indoor unit and ventilation unit within each G-50A .

G-50A selection:

Select the G-50 No.

Group No.:

Displays the group No.

Group information:

Displays the group configuration of the indoor unit or ventila- tion unit.

Unconnected indoor unit:

Displays the indoor unit, LOSSNAY (IC, KIC, AIC, LC) not set for the group.

Unconnected remote controller:

Displays the SC, GR, SR, AN, and RC which can be set for the group.

Confirm the group information. [Procedure]

1)Click the “/ ” button to select G-50 No.

Select the G-50A No. to be assigned using the “/ ” buttons.

2)Select the [OK] button after confirming the group information.

If it is not necessary to change or correct the information of each G-50A when it is checked, click the [OK] button.

*When the [Cancel] button is clicked, this setting is terminated to return to the initial window.

Change the group information. [Procedure]

1)Click the “/ ” button to select G-50 No.

Select the G-50A No. to be assigned using the “/ ” buttons.

2)Delete/add the unit icon.

Unit icon deletion:Click the unit icon to be deleted.

Unit icon addition:Click the unit icon to be added, from the Unconnected indoor unit and Unconnected remote controller columns to set it to the selected state. (The symbol of the selected unit is displayed by the pointer.)

When the group column to be added is clicked, the unit icon is displayed.

3)Select the [OK] button.

After fully completing the group information changes, click the [OK] button.

Note:

When the group setting change screen is changed, it is possible to reflect the changed contents on the G-50A system .

It cannot set the indoor unit (M-NET type), K control unit, A control unit, and LOSSNAY for the same group.

Since the number of groups and the number of indoor units connectable to the GR, SR, and AN is limited, set the group corresponding with such limitations.

This group setting screen displays the number of groups and number of indoor units which allow the GR, SR, AN, and SC to be newly organized.

Table: Number of management groups and number of indoor units

Symbol

Equipment name

Number of management groups

and number of indoor units

 

 

 

 

 

 

 

 

GR

Group remote controller

8 groups, 16 indoor units

 

 

 

 

 

SR

System remote controller

50

groups, 50

indoor units

 

 

 

 

 

AN

ON/OFF remote controller

16

groups, 50

indoor units

 

 

 

 

 

SC

System controller

50

groups, 50

indoor units

 

 

 

 

 

32