Monitoring operation amount data

 

 

[Procedure]

 

 

1) Click [Operation amount data monitor] icon.

 

 

 

Click the [Operation amount data monitor] icon of the

 

 

maintenance group in the initial window. The operation

 

 

amount data monitoring screen appears.

 

 

2) Set the interval to be monitored.

 

 

 

Use click and the “ / ” buttons to set the interval the

Operation amount data monitoring screen

 

running data held by the G-50A is to be monitored.

 

* Numbers can be manually input from the keyboard.

 

 

3) Click [OK] button.

 

 

 

When setting of the operation amount data monitor-

 

 

ing interval is complete, click the [OK] button. The

 

 

operation amount data monitor confirmation screen

 

 

appears.

 

 

* If the [Cancel] button is clicked, the settings are

 

 

interrupted and the screen returns to the initial

 

 

window.

 

 

4) Click [OK] button.

 

 

 

Confirm the monitoring interval at the operation amount

 

 

data monitor confirmation screen. After confirmation,

 

 

click the [OK] button. If it is determined automatically

 

 

that the monitor-prohibit time is applicable.

Operation amount data monitor

 

When it is out of the prohibited time range, the

confirmation screen

 

operation amount data monitor is started and the

 

 

message "Please wait a moment" is displayed on the

 

 

screen.

 

After the monitoring is terminated, the screen returns to the initial window.

Note:

The monitor of the operation amount data is intended for all indoor units for the object day, in which the contents are written over the PC database on which the integrated centralized control software (TG -2000A) operates. Monitor only the necessary date.

Since the monitor of the operation amount data requires time, wait for a moment until the monitor is terminated.

Monitor the data for the last day after 7:00.

Even if the operation amount data monitor is executed, it cannot use the results for the recalculation of proportionally divided power charges. In this case, use the “Maintenance of charge data” shown in 9.2 or the “Charging remedy ” shown in 9.5.

Note that the data is not reflected in the “Maintenance of charge data” screen even if the operation amount data is gathered using this function, but upon the output of the charge parameter data.

9.4Charge Parameter Output

This function is used to output the operation amount data (integrated capacity save ratio of indoor unit, integrated FAN operation time, integrated thermo-ON time, (integrated subsidiary heater operation time)) and charge parameters to the file.

Note:

The value stored in PC of TG-2000A is output unchanged. Contact us separately for the data generation method and other information.

*The values of the capacity save ratio, FAN operation time, thermo-ON time, and subsidiary heater operation time are integrated values. When the value exceeds “999999”, it is returned to “000000”.

The file output is executed for each G-50A.