Note:

Don’t change time in the following cases. However, this only applies when the charge function is on. Because charge collection processing is performed.

When the current time is between 04:00 and 07:00.

We recommend that the time be checked and corrected once a month.

Execute the correction of time within time of 08:00 to 21:45.When the RS -485 WHM is used, however, do not correct the time near the charge zone change time.

The date display order depends on the OS setting.

When the date is exceeded after the start of operation and the time is reset, air-conditioning charge calculation may not be performed correctly.

Maintenance Tip

Set these time and date settings from the TG-2000A application. When the TG-2000A program is running, do not change the Windows system time. Changing the Windows clock will not change the TG -2000A clock.

Don't change the date(and the time over the day), When charge function is used.Otherwise,the charge calculation may not be executed properly.

Monitor the time.

Monitor the year/month/day of the PC and connected G-50A . [Procedure]

1)Select [Time set -up] button.

Click the [Time set-up] button located in the system setting group on the initial window.

2)Select [Time monitor].

Click the [Time monitor] button on the time set-up select screen.

3)Select the [Monitor] button.

In this case, click the [Monitor] button on the time monitor screen. When the button is clicked, the differ- ence between the date/time of all G-50A units connected to the PC (personal computer) on which the integrated centralized control software TG -2000A operates and the reference machine is displayed.

* There is a difference of several seconds depending

Time monitor window

on the monitor timing.

 

4)Select [OK] button.

When the time confirmation is completed, click the [OK] button, and the initial screen returns.

 

Monitor button

Display of PC date/time

Difference from

reference machine

 

 

(G-50A No.1)

Display of G-50A

 

date/time

 